Cable HS XKDCu(Al)T 1000 mm² Cu 110 kV

Description

Description

Standards

  • Test
    IEC 60840; IEC 62067
  • National
    HD 632 Section O

Applications

This cable family is designed for strategic underground high-voltage links requiring very high reliability:

  • Underground high-voltage distribution networks
  • Installation in ducts, galleries or directly buried
  • Electrical substations and transformer stations
  • Infrastructures requiring service continuity and maximum safety
  • Critical industrial and energy applications

Key benefits

  • High-performance XLPE insulation ensuring excellent dielectric strength
  • Very good mechanical and environmental resistance
  • Radial and longitudinal water blocking to prevent moisture propagation
  • Robust HDPE sheath with low shrinkage rate
  • High durability for long-distance HV networks
  • Solution suited to strategic infrastructures

By choosing this range of high-voltage cables, you opt for a reliable, robust and durable solution, perfectly suited to the requirements of modern HV networks.

Characteristics

Characteristics

Dimensional characteristics

Dimensional characteristics

Conductor cross-section
1000 mm²
Conductor diameter
39.1 mm
Diameter over insulation
76.1 mm
Outer Diameter
89.6 mm
Screen section
95 mm²
Approximate weight
14.7 kg/m

Electrical characteristics

Electrical characteristics

Operating voltage
110 kV
Permissible short circuit current screen 1s
15.0 kA
Permissible short circuit current conductor 1s
143 kA
Max. DC resistance of the conductor at 20°C
0.018 Ohm/km
Nominal phase capacitance
0.23 µF / km
I max. @ 90°C-buried in trefoil joined
1050 A
I max. @ 90°C-buried in trefoil spaced
1185 A
I max. @ 90°C-buried in flat formation joined
1035 A
I max. @ 90°C-buried in flat formation spaced
1180 A
I max. @ 75°C-buried in trefoil joined
1030 A
I max. @ 75°C-buried in trefoil spaced
1065 A
I max. @ 75°C-buried in flat formation joined
920 A
I max. @ 75°C-buried in flat formation spaced
1060 A
Load factor
1
Sheaths grounding
1 point
Thermal soil resistivity dry zone
0.85 °K.m/W

Mechanical characteristics

Mechanical characteristics

Maximum tensile load during service (Tl)
4000.0 daN

Usage characteristics

Usage characteristics

Max. conductor temperature in service
90 °C
Short-circuit max. conductor temperature
250 °C
Ambient ground temperature
20 °C
Laying operation bending radius
3200 mm
Laying depth, center of system
1000 mm
Laying tube diameter
150 mm
Distance between tubes (X)
220 mm

Resources

Resources

Documentation

Construction pdf — 292.1 kB

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close

Contact us

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close